EARTH RESISTANCE MEASUREMENTS A PANACEA TO IMPROPER GROUNDING SYSTEM: A CASE STUDY OF ILARO TOWNSHIP

Sunday Olowofela, Samuel Omolola & Najeem Adelakun, July 2020, Published: 2020-11-12

Installation of electrical works in a building requires a proper investigation about the building, the purpose which the structure will serve, the soil resistance, and the type of installation required by competent personnel. However, inadequate study leads to several domestic accidents such as fire outbreak, burns, and electrical shock etc. Effective grounding of the electrical system set up a common reference potential for any kind of power supply system as a low resistance connection to earth is required. This investigation of the Electrical performance of the earth in Ilaro provides a valuable insight into how the standard earth resistance value can be achieved and maintained over the life of the installation with minimum cost and effort. For this research work, six (6) different locations were considered, measurements were taken using a digital Earth Resistance Meter, Global Positioning System with other test equipment at these locations and the empirical data gotten was analyzed graphically for each location. The result shows that the resistance of four (4) areas under test was relatively high and the remaining two (2) areas were low with values obtained ranging from 2.9Ω -5.5Ω. This reveeals that the resistance of the soil of Ilaro town is relatively high and not suitable for effective grounding without improving the conductivity of the soil.